Application Areas:

Fire stopping of penetrations with combustible pipes, with and without insulation

Suitable for installation in flexible walls, rigid walls and rigid floors

ETA configurations include include PVC-U, PE-HD and PP-H pipes, as well as various specific pipe systems

For reinstating the fire resistance of fire-rated wall and floor constructions at pipe penetrations

Advantages:

  • Certified fire protection
    • Fire protection collar consisting of a sheet steel housing with an intumescent inlay
    • Fire resistance classifications up to EI 120, depending on the approved application
    • European Technical Assessment ETA-23/0680 for pipe penetration seals
  • Versatile application
    • Suitable for combustible pipes with and without insulation
    • Suitable for plasterboard walls, rigid walls and rigid floors
    • Suitable for a wide variety of pipe types and installation configurations
  • Wide range of sizes
    • Collar sizes from Ø 32 to Ø 500 mm
    • Different collar dimensions available to suit the respective pipe size

Processing information

Install the fire protection collar on the surface of the building element in accordance with the applicable configuration specified in ETA-23/0680
For lightweight walls, fix the collar using continuous M8 threaded steel rods with M8 hexagon nuts
For solid walls and floors, fix the collar using 38 mm metal multi-purpose anchors with MMS-P 7.5 × 45 mm steel bolts and corresponding washers and nuts
Annular gaps up to a maximum width of 20 mm must be completely and tightly closed using the materials and arrangement specified for the respective construction and installation configuration in ETA-23/0680
Always observe the applicable installation configuration specified in ETA-23/0680

Advice

Fire resistance classifications up to EI 120, depending on the approved pipe and installation configuration
45° pipe penetrations are possible for selected pipe systems and installation configurations
Configurations with 2 × 45° pipe bends are approved for selected pipe systems
Selected applications are approved with PE or FEF pipe insulation
Sleeve installations and zero-distance configurations are approved for selected pipe systems and configurations
The applicable fire resistance classification depends on the pipe type, pype dimensions, insulation, supporting construction and installation configuration. Refer to ETA-23/0680 for the approved application